[A]
Absolute Humidity:
The weight of water vapor in a given amount of
air space. Absolute humidity is measured by grains per cubic foot.
Air Conditioner:
Assembly of equipment for the simultaneous
control of air temperature, relative humidity, purity, and motion.
Air Cooled:
Uses a fan to discharge heat from the
condenser coil to the outdoors.
Air-Cooled System:
A type of air conditioning system that uses
freon as a refrigerant and air as a condensing medium. Typically, the
air-cooled condenser is located outside and refrigerant lines are piped to it
from the indoor unit.
Air Diffuser:
Air distribution outlet or grille designed to
direct airflow into desired patterns.
Air Flow:
The distribution or movement of air.
Air Handler:
The portion of the central air conditioning or
heat pump system that moves heated or cooled air throughout a home's ductwork.
In some systems a furnace handles this function.
Annual Fuel Utilization Efficiency (AFUE):
A rating that denotes the efficiency of gas
heating equipment. It is the amount of heating your equipment delivers for
every dollar spent on fuel. A higher rating indicates more efficient equipment.
This rating is calculated in accordance with the Department of Energy test
procedures.
ARI
Air-Conditioning and Refrigeration Institute
is a non-profit, voluntary organization comprised of heating, air conditioning
and refrigeration manufacturers. ARI publishes standards for testing and rating
heat pumps and air conditioners to provide you with a standardized measure of comparison.
So, ARI ensures a level of quality within the industry.
Atmospheric Pressure:
The weight of a 1 square inch column of the
earth's atmosphere. At sea level this pressure is 14.696 pounds per square
inch.
Auto Changeover:
A control package that provides for automatic
switching from a primary air conditioning system to a backup in the event of a
failure of the primary system.
[B]
Balance Point:
An outdoor temperature, usually between 30° F
and 45° F, at which a heat pump's output exactly equals the heating needs of
the home. Below the balance point, supplementary electric resistance heat is
needed to maintain indoor comfort.
Bimetal:
Two metals with different rates of expansion
fastened together. When heated or cooled they will warp and can be made to open
or close a switch or valve.
Blower:
An air handling device for moving air in a
distribution system.
Boiling Point:
The temperature at which the addition of any
heat will begin a change of state from a liquid to a vapor.
BTU (British Thermal Unit):
The standard of measurement used for measuring
the amount of heat required to raise the temperature of one pound of water by
one degree (Fahrenheit). BTUH - The number of BTUs in an hour.
BTU/hr:
The abbreviation for British thermal units per
hour. The amount of heat required to raise one pound of water one degree
fahrenheit per hour, a common measure of heat transfer rate.
[C]
Capacity:
The ability of a heating or cooling system to
heat or cool a given amount of space. For heating, this is usually expressed in
BTU's. For cooling, it is usually given in tons.
Carbon Monoxide:
Carbon Monoxide (CO) is a colorless, odorless
gas produced by burning any fuel. CO is poisonous and symptoms of CO poisoning
are similar to those of the flu: headaches, fatigue, shortness of breath,
nausea and dizziness. The Consumer Product Safety Commission (CPSC) recommends
a yearly, professional inspection.
Central Air Conditioner System:
System in which air is treated at a central
location and carried to and from the rooms by one or more fans and a system of
ducts.
Centrifugal Compressor:
A type of compressor used in vapor compression
refrigeration cycles where a rotating impeller is the device which compresses
the refrigerant vapor. The vapor is drawn into the impeller axially, and is
discharged radially after energy is added to the vapor within the impeller.
Centigrade (Measure of Temperature):
A temperature scale with the freezing point of
water 00 and the boiling point 1000 at sea level.
CFM (Cubic Feet per Minute):
The abbreviation for cubic feet per minute,
commonly used to measure the rate of air flow in an air conditioning system.
Charge:
Amount of refrigerant in a system.
Chilled Water System:
A type of air conditioning system that has no
refrigerant in the unit itself. The refrigerant is contained in a chiller,
which is located remotely. The chiller cools water, which is piped to the air
conditioner to cool the space.
Comfort Air Conditioning:
Comfort air conditioning systems are designed
for the comfort of people, not the protection of computer-based electrical
systems. Unlike people, computers generate dry (sensible) heat, but not
humidity. Only about 60-70% of a comfort system's total capacity is dedicated
to the removal of sensible heat, while 30-40% is for dehumidification. With a
large percentage of their total capacity devoted to the removal of moisture,
comfort systems can lower room humidity far below acceptable standards. A
larger comfort system is required to obtain the same sensible capacity as a
precision cooling system.
Compressor:
The pump that moves the refrigerant from the
indoor evaporator to the outdoor condenser and back to the evaporator again.
The compressor is often called "the heart of the system" because it
circulates the refrigerant through the loop.
Compression:
The reduction of volume of a vapor or gas by
mechanical means.
Compression Ratio:
The ratio determined by dividing the discharge
pressure, in PSI, by the suction pressure in PSI.
Condensation:
The process by which a gas is changed into a
liquid at constant temperature by heat removal.
Condensation Point:
The temperature at which the removal of any
heat will begin a change of state from a vapor to a liquid.
Condenser:
A device that transfers unwanted heat out of a
refrigeration system to a medium (either air, water, or a combination of air
and water) that absorbs the heat and transfers it to a disposal point. There
are three types of condensers: air-cooled condensers, water-cooled condensers,
and evaporative condensers. The evaporative condenser uses a combination of air
and water as its condensing medium. Most residential systems have an air-cooled
condenser.
Condenser Coil:
A series or network of tubes filled with
refrigerant, normally located outside the home, that removes heat from the hot,
gaseous refrigerant so that the refrigerant becomes liquid again.
Condensing Unit:
Part of a refrigerating mechanism which pumps
vaporized refrigerant from the evaporator, compresses it, liquefies it in the
condenser and returns it to the refrigerant control. The outdoor portion of a
split system air conditioner contains the compressor and outdoor coil ignoring
the reverse cycle operation, also the outdoor in a heat pump system.
COP (Coefficient of Performance):
This is a measure of the energy efficiency of
a chiller.
Cooling Anticipator:
A resistance heater (usually not adjustable)
in parallel with the cooling circuit. It is 'on' when the current is
'off", adding heat to shorten the off cycle.
Cooling Capacity:
A measure of the ability of a unit to remove
heat from an enclosed space. COP - Coefficient of Performance of a heat pump
means the ratio of the rate of useful heat output delivered by the complete
heat pump unit (exclusive of supplementary heating) to the corresponding rate
of energy input, in consistent units and under operating conditions.
Cooling Load:
Heat which flows into a space from outdoors
and/or indoors.
[D]
Damper:
Found in ductwork, this movable plate opens
and closes to control airflow. Dampers are used effectively in zoning to
regulate airflow to certain rooms.
Defrost Cycle:
The process of removing ice or frost buildup
from the outdoor coil during the heating season.
Dehumidification:
The reduction of water vapor in air by cooling
the air below the dew point; removal of water vapor from air by chemical means,
refrigeration, etc.
Department of Energy (DOE):
A federal agency that sets industry efficiency
standards and monitors the use of various energy sources.
Direct Expansion Systems:
One of two types of basic cooling media (the
other is chilled water). Direct expansion systems utilize freon for cooling and
dehumidification. The three most common methods of heat rejection are air
cooled, water cooled and glycol cooled.
Direct Vent:
Pulls outside air for combustion and vents
combustion gases directly outside.
Downflow:
Refers to a type of precision air conditioning
system that discharges air downward, directly beneath a raised floor, commonly
found in computer rooms and modern office spaces.
Downflow Furnace:
A furnace that pulls in return air from the
top and expels warm air at the bottom.
Duct:
A pipe or closed conduit made of sheet metal,
fiberglass board, or other suitable material used for conducting air to and
from an air handling unit.
Ductwork:
Pipes or channels that carry air throughout a
building.
[E]
Economizer:
In a chiller with a two-stage centrifugal
compressor, the discharge from the first stage impeller and the inlet to the
second stage impeller are at a pressure level approximately half way between
the cooler pressure and condenser pressure. With this arrangement, an
economizer may be used. This is a shell within which refrigerant liquid from
the condenser drops down to the interstage pressure, flashing off some of the
refrigerant which is drawn directly into the second stage impeller. This
reduces the amount of refrigerant which has to be compressed by the first stage
impeller, improving the refrigeration cycle efficiency.
Efficiency
A rating on comfort equipment is similar to
the miles per gallon rating on your car. The higher the rating number, the more
efficient the system and the lower your fuel consumption will be.
Electronic Air Cleaner:
An electronic device that filters out large
particles and contaminants in indoor air. It then electronically pulls
out tiny particles that have been magnetized, such as viruses and bacteria,
drawing them to a collector plate.
Emergency Heat (Supplemental or Auxillary Heat):
The back-up heat built into a heat pump
system.
Energy Efficiency Ratio (EER):
Means the ratio of the cooling capacity of the
air conditioner in British Thermal Units per hour, to the total electrical
input in watts under ARI-specified test conditions.
Evaporator Coil:
A series or network of tubes filled with
refrigerant located inside the home that take heat and moisture out of indoor
air as liquid refrigerant evaporates.
[F]
Fahrenheit (Represented as degrees "F"):
The scale of temperature measurement most
commonly used in the United States of America.
Filter:
A device used to remove dust and other
particles from air for the purposes of reducing the load on the respiratory
system and to protect the HVAC equipment. Filters vary greatly in particle
arrestance; the higher the MERV rating, the better the filter.
Freon:
A general term used to identify, any of a
group of partially or completely halogenated simple hydrocarbons containing
fluorine, chlorine or bromine, which are used as refrigerants.
Furnace:
That part of an environmental system which
converts gas, oil, electricity or other fuel into heat for distribution within
a structure.
[G]
Glycol-Cooled System:
A type of air conditioning system that uses
freon as a refrigerant and a water/glycol solution as a condensing medium.
Typically, the glycol-cooled condenser is located inside the air conditioner
with the rest of the refrigeration components. Water/glycol is piped to the
unit from a drycooler or other suitable source. The glycol keeps the solution
from freezing during winter operation.
Ground Water-Source:
Water from an underground well is being used
as the heat source or heat sink for a heat pump.
[H]
Heat Exchanger:
A device for the transfer of heat energy from
the source to the conveying medium.
Heat Gain:
The amount of heat gained, measured in BTU's,
from a space to be conditioned, at the local summer outdoor design temperature
and a specified indoor design condition.
Heat Loss:
The amount of heat lost, measured in BTU's
from a space to be conditioned, at the local winter outdoor design temperature
and a specified indoor design condition.
Heat Pump:
An air conditioner that contains a valve that
allows it to alternate between heating and cooling.
Heat Source:
A body of air or liquid from which heat is
collected. With any heat pumps, the air outside the home is used as the heat
source during the heating cycle.
Heat Transfer:
The movement of heat from one place to
another, between two substances, or within a substance.
Heating Capacity:
The rate at which a specific device can add
substantial heat to a substance, expressed in BTUh (British Thermal Units per
hour).
Heating Seasonal Performance Factor (HSPF):
means the total heating output of a heat pump
in British Thermal Units during its normal usage period for heating divided by
the total electrical energy input in watt-hours during the same period.
Horizontal Furnace:
A furnace that lies on its side, pulling in
return air from one side and expelling warm air from the other.
HVAC:
Heating, Ventilation,
and Air Conditioning.
Humidification:
The process of adding moisture to the air
within a space.
Humidistat:
A device designed to regulate humidity input
by reacting to changes in the moisture content of the air.
Humidity:
The amount of moisture in the air. Air
conditioners remove moisture for added comfort.
[I]
Indoor Unit:
This is usually located inside the house and
contains the indoor coil, fan, motor, and filtering device, sometimes called
the air handler.
Indoor Coil:
Refrigerant containing portion of a fan coil
unit similar to a car radiator, typically made of several rows of copper tubing
with aluminum fins.
Infiltration:
Air flow into a space usually through walls
and leaks around doors and windows.
Insulation:
Any material that slows down the transfer of
heat.
[J]
No Definitions at this time.
[K]
Kilowatt (kW):
Equal to 1,000 watts. Kilowatt-hour (kWh) - A
common unit of electrical consumption measured by the total energy created by
one kilowatt in one hour.
[L]
Latent Cooling Capacity:
An A/C system's capability to remove moisture
from the air.
Latent Heat:
The heat energy needed to change the state of
a substance (i.e.: from a liquid to a gas) but not it's temperature.
Load Calculation:
A mathematical design tool used to determine
the heat gain and heat loss in a building so that properly sized air
conditioning and heating equipment may be installed.
[M]
Matched System:
A heating and cooling system comprised of
products that have been certified to perform at promised comfort and efficiency
when used together, and used according to design and engineering
specifications.
Microprocessor Controls:
A control system that uses computer logic to
operate and monitor an air conditioning system. Microprocessor controls are
commonly used on modern precision air conditioning systems to maintain precise
control of temperature and humidity and to monitor the units operation.
[N]
Natural-Draft Furnace:
A furnace in which the natural flow of air
from around the furnace provides the air to support combustion. It also depends
on the pressure created by the heat in the flue gases to force them out through
the vent system.
[O]
Operating Cost:
The day-to-day cost of running your home
comfort equipment, based on daily energy use.
Outdoor Coil/Condensing Unit:
The portion of a heat pump or central air conditioning
system that is located outside the home and functions as a heat transfer point
for collecting heat from and dispelling heat to the outside air.
[P]
Package System:
A piece of air conditioning and heating
equipment where all components are located in one cabinet. Used occasionally in
residential applications, the package unit is installed either beside or on top
of the home.
Packaged Unit:
A self-contained heating and/or air
conditioning system.
Payback Analysis:
Overall measure of the efficiency and value of
your home comfort system. By combining your purchase price and ongoing
operating costs, a payback analysis determines the number of years required
before monthly energy savings offset the purchase price.
Precision Air Conditioning:
Precision A/C systems are primarily designed
for cooling electronic equipment, rather than people. These pre-packaged
systems offer excellent reliability and typically have a high ratio of
sensible-to-total cooling capacity and a high CFM/ton ratio.
Purge Device:
A device which removes air and water vapor
from the refrigerant inside a chiller. A purge is a necessity in negative
pressure designs, but is not necessary in positive pressure designs where air
and water vapor are kept out of the system by the internal pressure.
[Q]
No Definitions at this time.
[R]
Refrigerant:
A substance that produces a refrigerating
effect while expanding or vaporizing.
Refrigerant Lines:
Set of two copper lines connecting the outdoor
unit and the indoor unit.
Register:
Combination grille and damper assembly
covering an air opening or end of an air duct.
Relative Humidity:
The ratio of the amount of vapor contained in
the air to the greatest amount the air could hold at that temperature. Normally
expressed as a percentage.
Return Air:
Air drawn into a heating unit after having
been circulated from the heater's output supply to a room.
Reversing Valve:
A device in a heat pump that reverses the flow
of refrigerant as the system is switched from cooling to heating.
[S]
SEER (Seasonal Energy Efficiency Ratio):
A rating that denotes the efficiency of air
conditioning equipment. It is the amount of cooling your equipment delivers for
every dollar spent on electricity. It is the ratio of cooling delivered by a
system, measured in BTUs, to the dollar cost of the electricity to run the
system, as measured in watt-hours. This ratio is determined using specified
federal test procedures. The higher the SEER, the more efficient the unit. The
more efficient the unit, the lower the operating cost.
Sensible Cooling Capacity:
An A/C system's capability to remove heat from
the air. (lower the temperature).
Sensible Heat:
Heat energy that causes a rise or fall in the
temperature of a gas, liquid or solid when added or removed from that material.
Sensible heat changes the temperature by changing the speed at which the
molecules move.
Setpoint:
The temperature to which a thermostat is set
for desired comfort level.
Single Package:
A year-round heating and air conditioning
system that has all of the components completely encased in one unit outside
the home.
Split System:
A central air conditioner consisting of two or
more major components. The system usually consists of a compressor-containing
unit and condenser, installed outside the building and a non-compressor -
containing air handling unit installed within the building. This is the most
common type of system installed in a home.
Storage Tank:
A steel shell in which the refrigerant charge
for a chiller may be temporarily stored while the chiller is serviced.
Supercooled Liquid:
Liquid refrigerant cooled below its saturation
point.
Subcooler:
This is a section of some condensers in which
the temperature of the condensed refrigerant liquid is reduced. This improves
the energy efficiency of the chiller.
Subcooling:
Creating a drop in temperature by removing
sensible heat from a refrigerant liquid.
Superheated Vapor:
Refrigerant vapor heated beyond its saturation
point.
Superheating:
Creating a rise in temperature by adding heat
energy to a refrigeration vapor.
Supplementary Heat:
The auxiliary or emergency heat, usually
electrical resistance heat, provided at temperatures below a heat pump's
balance point.
Switchover:
A device in a heat pump that reverses the flow
of refrigerant as the system is switched from cooling to heating.
[T]
Temperature:
The measure of the intensity of heat that a
substance possesses.
Thermostat:
A temperature control device, typically found
on a wall inside that consists of a series of sensors and relays that monitor
and control the functions of a heating and cooling system.
Tonnage:
The unit of measure used in air conditioning
to describe the cooling capacity of a system. One ton of cooling is based on
the amount of heat needed to melt one ton (2000 lbs.) of ice in a 24 hour
period. One ton of cooling is equal to 12,000 Btu/hr.
[U]
Upflow:
A type of air conditioning system that
discharges air into the conditioned space via a top-mounted discharge plenum or
through an overhead duct system.
Upflow Furnace:
A furnace that pulls return air in from the
bottom and expels warm air from the top.
[V]
Vacuum Pump:
A pump used to remove air and moisture from a
refrigeration system at a pressure below atmospheric pressure.
Vapor Barrier:
A moisture-impervious layer applied to the
surfaces enclosing a humid space to prevent moisture travel to a point where it
may condense due to lower temperature.
Vapor Seal:
A vapor seal is an essential part of
preventing moisture infiltration into or migration out of a critical space, such
as a data processing center or other room that contains sensitive electronic
instrumentation. Essentially, a vapor seal is a barrier that prevents air,
moisture, and contaminants from migrating through tiny cracks or pores in the
walls, floor, and ceiling into the critical space. Vapor barriers may be
created using plastic film, vapor-retardant paint, vinyl wall coverings and
vinyl floor systems, in combination with careful sealing of all openings (doors
and windows) into the room.
Ventilation:
The process of supplying or removing air, by
natural or mechanical means, to or from any space. Such air may or may not have
been conditioned.
Ventilator:
A ventilator captures heating or cooling
energy from stale indoor air and transfers it to fresh incoming air.
[W]
Water Cooled System:
A type of air conditioning system that uses
freon as a refrigerant and water as a condensing medium. Typically, the
water-cooled condenser is located inside the air conditioner with the rest of
the refrigeration components. Water is piped to the unit from a cooling tower
or other suitable source.
Water Source:
Water is being used as the heat source or heat
sink for a heat pump. Sources of underground water are wells and sources of
surface water are lakes, large ponds, and rivers.
Watt:
A unit of power that equals one joule per
second. Named after James Watt.
[X]
No Definitions at this time.
[Y]
Year-Round:
Air Conditioner which uses gas or oil for
heating.
[Z]
Zone System:
A method of dividing a home into zones and
enabling you to control the amount of comfort provided to each.
Zoning:
The practice of providing independent heating
and/or cooling to different areas in a structure. Zoning typically utilizes a
system controller, zoning dampers controlled by a thermostat in each zone, and
a bypass damper to regulate static pressure in the supply duct.